N2XS(F)2Yy

General information

Standard: AZS 418-2010 (TS İEC 60502-2), TSE K 204 The Russian analogue: PvPug They are used for stationary laying in the ground and trenches, regardless of the degree of soil and water corrosiveness. The cable sealing allows it to be used on the ground with high humidity and in partially submerged installations, while observing safety rules and providing protection against mechanical damage. It is possible to use them without protection from solar radiation in the open air, as well as in cable lines (under the condition of using a sheath that meets the conditions of fire safety). It is allowed to install cables of this brand on complicated cable routes. Cables can be installed without restrictions on the level difference.

Single-core XLPE insulated, copper conductor high voltage cable sheathed with the increased density polyethylene (PE) and a semi-conductive water-blocking tape

Structure:

  1. The conductor is copper, multi-wire compacted, round form, corresponds to class 2 of IEC 60228
  • The cross-section of a multi-wire compacted round conductor is 25÷800 mm2
  • The cross-section of a multi-wire compacted round conductor, consisting of 5 sectors, is 1000÷1600 mm2
  1. The outer conductor screen is made of extruded semiconducting cross-linked polyethylene
    3. Insulation is cross-linked polyethylene (2X)
    4. Insulation screen is made of extruded semiconducting cross-linked polyethylene
    5. The separation layer is made of semi-conductive water-blocking tape
    6. The screen of copper wires fastened with copper tape (S)

Minimum cross-section of screen for cables with a conductor cross-section of 25-120 mm2 is 16 mm2
Minimum cross-section of screen for cables with a conductor cross-section of 150-300 mm2 is 25 mm2
Minimum cross-section of screen for cables with a conductor cross-section of 400-1000 mm2 is 35 mm2
Minimum cross-section of screen for cables with a conductor cross-section of 1200 mm2 and above is 50 mm2

The maximum cross-section of screen can be set based on the customer's request.

  1. The separation layer is made of semi-conductive water-blocking tape (F)
    8. The outer protective shell is made of packed polyethylene (2Yy)

Specifications:

  • Operating conductor temperature: +90 0C
  • The maximum heating temperature of the cable conductors in case of emergency: +130 0C
  • The maximum heating temperature of the cable conductors in case of a short circuit: +250 0С
  • The duration of a short circuit (not more than): 5 seconds
  • Cable laying temperature (not less than): -15 0С
  • Ambient temperature: -60 / +50 0C
  • Minimum bending radius of the cable: 15xD (D – outer diameter of the cable)

NOTE: Technical specifications are given in Table 1.